Product Name: Eight Channel RTD Module
Brand Name: EMERSON Westinghouse
Model Number:5X00119G01
Country of Origin: USA
Warranty: 12 Months
Whatsapp:+86 18159889985
Email:[email protected]
Brand Name: |
Westinghouse |
Model Number: |
5X00119G01 |
Country of Origin: |
USA |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
in stock |
Payment Terms: |
T/T |
|
Sales Manager: |
Stella |
|
Send an email: |
|
|
Contact in Whatsapp: |
|
Parameter |
Specification |
|
Model |
5X00119G01 (Electronics Module / EMOD) |
|
Manufacturer |
Emerson (formerly Westinghouse) |
|
Product Family |
Ovation Distributed Control System (DCS) |
|
Product Type |
8-Channel RTD Input Module |
|
Channels |
8 independent RTD input channels |
|
Compatible Personality Module |
5X00121G01 (required; not CE Mark certified) |
|
RTD Types Supported |
Pt100, Pt500, Cu100, Ni100, Cu50, Cu53 |
|
Wiring Configurations |
2-wire, 3-wire, or 4-wire |
|
Resolution |
12-bit |
|
Accuracy (@25°C) |
0.10% ± [0.045(Rcold/Rspan)]% ± [(Rcold + Rspan)/4096 OHM]% ± [0.5 OHM/Rspan]% ± 10 µV ± 1/2 LSB |
|
Temperature Coefficient |
10 ppm/°C |
|
Input Impedance |
100 MΩ (normal); 50 kΩ (power-down) |
|
Sampling Rate (60 Hz) |
20/sec normally; drops to 2/sec during 3-wire lead resistance measurement (every 6.45 sec) |
|
Sampling Rate (50 Hz) |
16.67/sec normally; drops to 3/sec during 3-wire lead resistance measurement (every 6.45 sec) |
|
Self-Calibration Mode |
On demand; rate drops to 1/sec during cycle |
|
Dielectric Isolation (Channel-to-Channel) |
200 V AC/DC |
|
Dielectric Isolation (Channel-to-Logic) |
1000 V AC/DC |
|
Common Mode Rejection |
120 dB @ DC and nominal line frequency ±1/2% |
|
Normal Mode Rejection |
100 dB @ DC and nominal line frequency ±1/2% |
|
Module Power Consumption |
3.6 W typical; 4.2 W maximum |
|
Power Supply |
24 V DC |
|
Operating Temperature |
0°C to +60°C (32°F to 140°F) |
|
Storage Temperature |
–40°C to +85°C (–40°F to +185°F) |
|
Humidity |
0% to 95% (non-condensing) |
|
Weight |
Approx. 0.32 kg (0.7 lb) |
|
Compatibility |
Ovation DCS only; requires 5X00121G01 PMOD |
|
CE Mark |
Not applicable (module not CE Mark certified) |
The 5X00119G01 is an 8‑channel RTD input Electronics Module (EMOD) from Emerson‘s Ovation series, engineered for precision temperature measurement in distributed control systems. The 5X00119G01 converts resistance signals from Resistance Temperature Detectors (RTDs) into digital data for the Ovation controller. Supporting Pt100, Pt500, Cu100, and Ni100 sensors in 2‑, 3‑, or 4‑wire configurations, the 5X00119G01 delivers 12‑bit resolution with 0.10% accuracy. The 5X00119G01 must be paired with the 5X00121G01 Personality Module (PMOD) to form a complete input assembly. With 1000 V channel‑to‑logic isolation and on‑demand self‑calibration, the 5X00119G01 ensures reliable performance in demanding industrial environments.
High Channel Density – 8 RTD inputs per module maximise I/O capacity while minimising chassis space requirements, reducing overall system footprint.
Superior Signal Integrity – 1000 V AC/DC channel‑to‑logic isolation and 120 dB common mode rejection protect against electrical noise and ground loops in harsh industrial environments.
Flexible Wiring Configurations – Supports 2‑wire, 3‑wire, and 4‑wire RTD connections on a per‑channel basis via configuration registers, accommodating diverse field installations.
On‑Demand Self‑Calibration – User‑initiated calibration ensures measurement accuracy without removing the module from service, reducing maintenance downtime.
Proven Ovation Platform – Designed specifically for Emerson‘s Ovation DCS, ensuring seamless system integration and long‑term reliability backed by decades of power and process industry experience.
Automatic Lead Resistance Compensation – In 3‑wire mode, the module periodically measures and compensates for lead resistance, eliminating a common source of temperature measurement error.
8 Independent RTD Input Channels – Supports Pt100, Pt500, Cu100, Ni100, and other RTD types
Flexible Wiring Support – Per‑channel configurable for 2‑wire, 3‑wire, or 4‑wire RTD connections
12‑Bit Resolution – Delivers precise temperature measurement with 0.10% accuracy at 25°C
High Isolation – 1000 V AC/DC channel‑to‑logic isolation for electrical safety and noise immunity
On‑Demand Self‑Calibration – User‑initiated calibration ensures ongoing measurement accuracy
Selectable 50/60 Hz Rejection – Configurable sampling rates optimised for power line noise rejection
Comprehensive Diagnostics – Channel error LEDs indicate overrange, underrange, or communication failure
Hot‑Swap Capable – Supports online module replacement without system shutdown
LED Status Indicators – Power (P), Communication (C), Internal Fault (I), and per‑channel error LEDs for rapid troubleshooting
Compatibility & Pairing
The 5X00119G01 EMOD must be paired with the 5X00121G01 Personality Module (PMOD). The two modules are not interchangeable with other Ovation I/O modules.
The module is not applicable for CE Mark certified systems.
Mounting
Install the EMOD + PMOD assembly into a standard Ovation I/O rack slot. The module is designed for standard rack installation.
Do not mount the module directly above high‑heat devices such as power supplies or terminal blocks carrying high‑current heater feeds.
Wiring
Field RTD sensors connect to the terminal block on the Personality Module (5X00121G01). A simplified wiring diagram label on the PMOD side indicates the correct terminal connections.
Use shielded twisted‑pair wiring for RTD connections to minimise electrical noise. Ground the shield at the module end only.
Per‑channel wiring configuration (2‑wire, 3‑wire, or 4‑wire) is set via configuration registers:
Address 13 (0xD), Bits 8–15: Set to 0 for 3‑wire, 1 for 4‑wire operation per channel.
Address 12 (0xC) and Address 14 (0xE): Configure channel scales (RTD type and range) for Channels 1–4 and 5–8 respectively.
Important: Configuring channel scales while the system is running will cause all channels to return an attention status for up to two seconds following reconfiguration.
Ensure proper lead resistance compensation for 3‑wire RTDs—lead resistance measurement occurs automatically every 6.45 seconds.
Power
The module is powered by the Ovation rack backplane. No separate field power connection is required.
Q1: Which Personality Module is required for the 5X00119G01?
A1: The 5X00119G01 must be paired with the 5X00121G01 Personality Module. The two modules are not compatible with other Ovation I/O modules.
Q2: Is the 5X00119G01 CE Mark certified?
A2: No. The 5X00119G01 and its companion 5X00121G01 are not applicable for CE Mark certified systems.
Q3: What RTD types and wiring configurations does the 5X00119G01 support?
A3: The module supports Pt100, Pt500, Cu100, Ni100, and other RTD types in 2‑wire, 3‑wire, or 4‑wire configurations, configurable per channel via register settings.
Q4: What is the accuracy of the 5X00119G01?
A4: The module provides 0.10% accuracy at 25°C with 12‑bit resolution. The temperature coefficient is 10 ppm/°C.
Q5: How many channels does the 5X00119G01 provide?
A5: The 5X00119G01 provides 8 independent RTD input channels, making it suitable for multi‑point temperature monitoring applications in power generation, chemical processing, and other industrial environments.