Minimum quantitas ordinis |
1 piece |
Pretium |
Contactus pro Jim |
Singula Packaging |
Novus Originalis, Sigillatus a Fabrica |
Tempus Traditionis |
3–7 dies |
Condiciones solutionis |
T/T |
Shipping modum |
DHL / FedEx / UPS / TNT |
Capacitas Supplicandi |
In stoce |
|
Numerus Exemplaris
|
6GK1415-2AA10
|
|
AS-Interface Specification
|
V3.0
|
|
Profilum Magistri AS-i
|
M4
|
|
AS-Interface connections
|
1
|
|
RS485 connections
|
1
|
|
Maximum Servi AS-i
|
62
|
|
Maximum Intrōdūctiōnum AS-i
|
496
|
|
Maximum Extrāductiōnum AS-i
|
496
|
|
AS-i cycle with 31 slaves
|
5 ms
|
|
AS-i cycle with 62 slaves
|
10 ms
|
|
Origō Suppeditātiōnis
|
AS-Interface cable
|
|
Current at 30 V
|
maxime 200 mA
|
|
Ammissio Potentiae
|
4.5 W
|
|
Tensionis insulatio evaluata
|
500 V
|
|
AS-i Connection
|
Fistulae fixationis
|
|
Horizontal-rail operating temperature
|
0–60 °C
|
|
Vertical-rail operating temperature
|
0–45 °C
|
|
Trānsportus temperatūra
|
−40 ad +70 °C
|
|
Temperatura servandae
|
−40 ad +70 °C
|
|
Maxima humiditas relativa ad 25 °C
|
95%
|
|
Altitudo Installationis Maxima
|
2000 m above sea level
|
|
Aestimatio Protectionis
|
IP20
|
|
Rail de montage
|
35 mm DIN-rail
|
|
Diodi Luminis Status
|
PWR, APF, CER, AUP, CM, BF, SF
|
|
Marking for hazardous gas
|
II 3 G Ex ec IIC T4 Gc
|
|
Access to digital data
|
Process image / peripheral addresses
|
|
Access to analog data
|
Transfer of data records
|
|
Dispositio Redundantiae
|
Supported with Y-Link
|
|
AS-i Potentia24V
|
Non sustentatum
|
|
Salus Protocolla
|
ASIsafe and PROFIsafe not supported
|
|
Isolatio galvanica
|
Praebitum
|
|
VENDITE
Iimus Pei
|
Epistula electronica
|
Telephus WhatsApp
|
Siemens 6GK1415-2AA10 is the SIMATIC NET DP/AS-Interface Link 20 E gateway. It connects an AS-Interface network to PROFIBUS DP. The gateway complies with AS-Interface specification V3.0 and supports the M4 master profile. Up to 62 AS-i slaves can be connected. The device is supplied through the AS-i cable.
Digital I/O is accessed through process-image or peripheral addressing. Analog I/O is transferred through data records. Configuration is available through the device pushbutton, STEP 7, GSD or the command interface. Status LEDs assist local commissioning and fault checks. This order number is not intended for safety-related control functions.
|
KFD2-UT2-1 191884 KHA6-SR2-EX2.W 33804S PCO5 PCO5000000AS0
DIM-6CH-2A Duc001 ir425-D4-2
MK8050GACY HDD2E46 PXA30-K11 LT-840-350
QSNE-4S10-D CONTREXGRP/1/PV2122-01077-1 PGDT04000F020
8323 / ID-NO.417727L TSC2 VCL-E1-030
KP551 DMC-C 6504086 VIO-25/60
CR1021-04 7KG2109-2ZZ13-9B IS-485L
IP-2G4A UDS1100002-01 08-358-013-R KFDO-HMS-16
AKM115F120 Brady 76627 AV3116DNv1
PCO2DA0BM0 PS4-101-DD1 PR 4114 4501
TZ370 APL57-100 CH-104570-026 SDU101 F004
DM4T 4940275 BF80 11BF8000230 Brady 76688
C0-E1-11AAR aci1230 FX-PCG2621-0
|