Product Name: 16 fold output module
Brand Name: HIMA
Model Number:F3322
Country of Origin:GERMANY
Warranty: 12 Months
Whatsapp:+86 18159889985
Email:[email protected]
Brand Name: |
HIMA |
Model Number: |
F3322 |
Country of Origin: |
GERMANY |
Packaging Details: |
Original new Factory Sealed |
Delivery Time: |
Delivery time in stock |
Payment Terms: |
T/T |
Supply Ability: |
in stock |
|
Sales Manager: |
Stella |
|
Send an email: |
|
|
Contact in Whatsapp: |
The F3322 is a 16‑channel digital output module from HIMA‘s HIQuad series, engineered for safety‑critical applications within HIMA H41q and H51q safety PLC systems. The F3322 provides transistor outputs configurable as open‑collector or push‑pull, supporting resistive and inductive loads up to 0.5 A per channel. With SIL 3 certification, ≥2.5 kV isolation, per‑channel diagnostics, and failsafe behavior upon L‑supply loss, the F3322 delivers reliable, high‑integrity output control for emergency shutdown (ESD), fire & gas (F&G), and burner management systems (BMS).
Digital Output Actuation – Converts logic commands into 16 independent digital output signals (0 or 1) to control relays, solenoids, actuators, and indicators
Load Switching – Drives resistive loads (e.g., heaters), inductive loads (e.g., solenoids, motor starters), and lamp loads up to 12 W per channel
Failsafe Behavior – Upon L‑supply break, all outputs are immediately de‑energised (no output signal), ensuring a safe state
Short‑Circuit & Overload Protection – Built‑in current limiter (>550 mA trip point) protects the module and field wiring
System Diagnostics – Per‑channel self‑diagnostics with independent Power/Error LED indicators for rapid troubleshooting
16 Independent Output Channels – High‑density digital output capability in a compact 4 TE footprint
Two Output Modes – Configurable as open‑collector (for relay/contact loads) or push‑pull (for higher current LED and logic loads)
SIL 3 Safety Certification – TÜV‑certified per IEC 61508 for safety instrumented systems up to SIL 3 / AK 7
High Channel Isolation – ≥2.5 kV DC isolation between outputs and system, preventing fault propagation
Failsafe Output Behaviour – Outputs de‑energise upon loss of L‑supply, ensuring a safe state
Robust Protection – Short‑circuit proof outputs with current limiter trip point >550 mA
Comprehensive Diagnostics – Per‑channel self‑diagnostics with independent Power/Error LED status indicators
Hot‑Swap Capable – Supports online module replacement without system shutdown
Wide Temperature Operation – Industrial‑grade from –25°C to +70°C
Mounting – Install the F3322 module into a standard 19″ Eurocard rack (6U form factor) with hot‑swap support. The module occupies 4 TE of rack space.
Maximum Module Density – A maximum of 10 fully loaded F3322 modules may be installed per I/O subrack.
Load Capacity Planning – The total simultaneous output load must not exceed 8 A (50% of 16 × 0.5 A). Ensure the rack‘s standard 4 A slow‑blow fuse is suitable for the total load.
Wiring Connections – Use the designated 2‑pole connection terminals for each output channel. For cable assemblies, refer to the Z 7136 / 3322 / C. / P2 cable plug with 2‑pole connection and lead marking.
Cable Specifications – Maximum line length: 750 mm; recommended cable type: LiYY 16/32 × 0.5 mm².
Power Supply – The module requires 24 VDC field supply plus 5 VDC logic supply from the backplane.
Fusing – The I/O rack is typically equipped with a 4 A slow‑blow fuse for the module group.
Q1: What is the maximum load current per output channel?
A1: Each of the 16 channels supports a maximum continuous load current of 0.5 A (500 mA) at 24 VDC.
Q2: Can all 16 outputs be operated at full load simultaneously?
A2: No. The total simultaneous output load must not exceed 8 A (50% of 16 × 0.5 A). Exceeding this limit may overload the power supply.
Q3: What happens if the L‑supply wire breaks?
A3: The module immediately de‑energises all output signals – a designed safety feature to ensure a fail‑safe state.
Q4: How many F3322 modules can be installed in one I/O subrack?
A4: A maximum of 10 fully loaded F3322 modules may be installed per I/O subrack to avoid overloading the power supply.
Q5: Is the F3322 suitable for safety‑critical applications?
A5: Yes. The F3322 is SIL 3 certified per IEC 61508 (TÜV) and features safety isolation, short‑circuit proof outputs, and failsafe behaviour upon L‑supply loss, making it ideal for ESD, F&G, and BMS applications.
Inquiry Now :[email protected]