ICS TRIPLEX Regent Safety System Guarded Analog Output Module T3480 In stock

Product Name:Guarded Analog Output Module

Brand Name: ICS TRIPLEX

Model Number:T3480

Country of Origin:USA

Warranty: 12 Months

Whatsapp:+86 18159889985

Email:[email protected]

  • Overview
  • Contact for quotation
  • Specifications
  • Description
  • Competitive Advantage
  • Features
  • Theory of Operation
  • FAQ
  • Recommended Products

Overview

Brand Name:

ICS TRIPLEX

Model Number:

T3480

Country of Origin:

USA

Packaging Details:

Original new Factory Sealed

Delivery Time:

Delivery time in stock

Payment Terms:

T/T

Contact for quotation

Sales Manager:

Stella

Send an email:

[email protected]

Contact in Whatsapp:

+86 18159889985

Specifications

Parameter

Specification

Model

T3480

Manufacturer

ICS Triplex (Rockwell Automation / Emerson)

Product Type

Guarded Analog Output Module

Architecture

Triple Modular Redundant (TMR) / Dual-redundant (Regent)

Output Channels

8 (Trusted TMR) / 6 (Regent)

Output Range

4-20 mA or 0-10 V (software-selectable)

Resolution

12-bit

Output Accuracy

±0.5% FS (typical); ±0.1% FS at 25°C

Load Capacity

0–750 Ω (current); >2 kΩ (voltage)

Isolation Voltage

2 kV RMS / 2500 V (field-logic)

Update Cycle

1 ms (typical)

SOE Resolution

1 ms, ±10 ms timestamp accuracy

Input Voltage

20–32 V DC (24 V DC nominal)

Power Consumption

≤1.5 W (typical) / 4.5 W (max)

Operating Temp

0°C to +60°C (standard); -40°C to +85°C (extended)

Protection Class

IP20 (chassis mount) / IP65 (enclosed variant)

Weight

0.4–1.28 kg (variant dependent)

Safety Rating

SIL 3 (IEC 61508), TÜV certified

Communication

Modbus RTU (RS-485) via Trusted backplane

Description

The T3480 is a high‑integrity guarded analog output module from ICS Triplex, engineered for safety‑critical applications in oil & gas, chemical, power generation, and turbomachinery control. The T3480 converts digital safety logic commands into precision 4‑20 mA or 0‑10 V signals to drive field devices such as control valves, actuators, and variable speed drives. Available in both Trusted TMR (8‑channel) and Regent (6‑channel) variants, the T3480 employs triple‑modular or dual‑redundant architectures with hardware‑level voting and comparison of drive/reference signals. With 12‑bit resolution, ±0.5% accuracy, 2 kV isolation, and SIL 3 certification, the T3480 delivers fail‑safe analog output for demanding safety instrumented systems (SIS).

Competitive Advantage

  • Hardware‑Level Redundancy – TMR architecture with 2oo3 voting; any single channel failure does not affect the output, and a second fault defaults to a safe state.

  • Drive‑Reference Comparison – Dual D/A converters per channel; output is only enabled when the drive and reference signals match, ensuring fail‑safe operation.

  • Hot‑Swappable – Modules can be replaced without system shutdown, minimizing downtime.

  • Parallel Redundancy – Two modules can be connected in parallel; standby module takes over in <5 ms with bumpless transfer.

  • SIL 3 Certified – TÜV‑certified per IEC 61508 for use in safety instrumented systems.

  • Comprehensive Self‑Diagnostics – Continuous monitoring of D/A converters, voter logic, and output loops; detects open/short circuits.

Features

  • 8 (Trusted) or 6 (Regent) isolated analog output channels

  • 4‑20 mA or 0‑10 V output (software‑configurable)

  • 12‑bit resolution with ±0.5% FS accuracy

  • 2 kV RMS galvanic isolation (channel‑to‑system)

  • 1 ms update cycle for fast loop response

  • 1 ms SOE recording with ±10 ms timestamp

  • Front‑panel LED indicators (active/fault, shutdown, per‑channel status)

  • Hot‑swappable; supports parallel redundant configuration

  • Built‑in loop integrity monitoring and self‑diagnostics

  • Wide operating temperature: -40°C to +85°C (extended variant)

  • TÜV SIL 3 certified (IEC 61508)

  • Modbus RTU communication via Trusted backplane

Theory of Operation

The T3480 receives triplicated write data commands from the processor over the I/O Safetybus. Onboard, the triplicated data are routed to two independent voter and logic sections. Each section independently votes the data and drives one 12‑bit D/A converter per output channel.

For each channel, one D/A converter generates the drive signal (actual output), while the other generates a reference signal. The module continuously compares these two signals; they must match for the output to be enabled. If they disagree, the module enters a fail‑safe state, shunting the output.

In parallel redundant configurations, two T3480 modules are cross‑strapped via STATUS OUT/IN signals. One module actively controls the load while the standby module tests its circuits with outputs shunted to AGND. If the active module fails, the standby takes over in <5 ms with bumpless transfer.

Comprehensive self‑testing covers D/A converters, voter logic, Safetybus interfaces, and output loops. Faults are annunciated via front‑panel LEDs and communicated to the system for predictive maintenance.

FAQ

Q1: What is the difference between the Trusted TMR and Regent versions of the T3480?
A1: The Trusted TMR T3480 features 8 output channels with triple‑modular redundancy (3 independent processing paths). The Regent T3480 has 6 channels with dual‑redundant design.

Q2: What output signals does the T3480 support?
A2: The T3480 supports both 4‑20 mA current loops and 0‑10 V voltage outputs, software‑selectable per channel.

Q3: Can the T3480 be replaced without shutting down the system?
A3: Yes. The T3480 is hot‑swappable. In parallel redundant configurations, either module can be removed while the other continues controlling the load without interruption.

Q4: What safety integrity level does the T3480 achieve?
A4: The T3480 is TÜV‑certified for SIL 3 per IEC 61508, suitable for use in safety instrumented systems (SIS).

Q5: How does the T3480 ensure fail‑safe operation?
A5: Each channel uses dual D/A converters—one for the drive signal and one for a reference. The output is only enabled when both signals match. If they differ, the module defaults to a safe state.

Inquiry Now : [email protected]