honeywell experion pks series c cc gaix11 redundant is analog input iota-0

HONEYWELL

Home >  Products >  HONEYWELL

Honeywell Experion PKS Series C CC-GAIX11 Redundant IS Analog Input IOTA

Honeywell Experion PKS Series C Redundant IS Analog Input IOTA
Complete Model
CC-GAIX11
Official Product Description
Redundant 12-inch intrinsically safe analog input I/O Termination Assembly for supported Series C high-level analog input modules.
CORE FEATURE: Redundant 16-channel analog-input termination with Series C intrinsically safe field interfacing.
LEAD TIME: In stock
WARRANTY: 1 year
Appurtenance
  • Overview
  • Technical Data
  • Inquiry
  • Functions & Security
  • Interfaces & Compatibility
  • Installation & Wiring
  • Operation & Maintenance
  • FAQ
  • Recommend Models
  • Recommended Products
Product Overview
CC-GAIX11 is the Honeywell Series C redundant I/O Termination Assembly listed for high-level analog input applications.
Honeywell lists CC-GAIX11 with supported CC-PAIH01 or CC-PAIH02 HART analog-input modules and CC-PAIX01 or CC-PAIX02 non-HART analog-input modules.
The official Series C function matrix identifies the CC-GAIX21 and CC-GAIX11 termination pair as the intrinsically safe option and specifies a nominal 12-inch redundant IOTA format.

Technical Data

Complete model
CC-GAIX11
Brand
Honeywell
Product family
Experion PKS Series C
Product type
Redundant intrinsically safe analog input IOTA
Redundancy
Redundant IOTA
Supported I/O function
High-level analog input with HART or without HART, according to the installed supported IOM
Supported IOMs
CC-PAIH01, CC-PAIH02, CC-PAIX01 and CC-PAIX02
Channel capacity
16 analog-input channels with a supported IOM
Input types
Voltage or current from 2-wire or self-powered transmitters, subject to the installed IOM configuration
Input ranges
0 to 5 V, 1 to 5 V, 0.4 to 2 V or 4-20 mA through 250 ohms with supported CC-PAIH02 or CC-PAIX02 configuration
A/D resolution
16 bits with the supported input module
Input scan rate
50 ms with the supported input module
Accuracy
+/-0.075% of full scale at 23.5 +/-2 degrees C; +/-0.15% from 0 to 60 degrees C with the supported input module
Dimensions
Nominal 12-inch (304 mm) redundant IOTA size; complete width, height and depth are not specified in the reviewed official specification
Weight
Not specified for CC-GAIX11 in the reviewed Honeywell official documentation
Operating temperature
Series C general limit: 0 to +60 degrees C internal cabinet ambient
Storage temperature
Series C general limit: -40 to +85 degrees C
Protection rating
Series C general rating: IP20 / NEMA 1
Official source
Honeywell EP03-490-520 Version 1.5, PDF pages 8 to 9 and 50; Series C platform EP03-520-515 pages 5 to 8

Inquiry

Functions & Security

Redundant termination
The 12-inch CC-GAIX11 accepts the documented redundant Series C analog-input configuration.
Intrinsic-safety option
Honeywell identifies the CC-GAIX11/CC-GAIX21 IOTA pair as the IS analog-input termination option.
HART or conventional AI
The termination is listed with supported high-level analog input IOMs with or without HART.
Series C maintenance design
The IOM plugs onto the IOTA so field termination and electronics are maintained in the same cabinet area.
Field wiring integration
Series C IOTAs provide on-board signal termination and field-power distribution for the engineered configuration.

Interfaces & Compatibility

IOM interface
Use only the supported CC-PAIH01, CC-PAIH02, CC-PAIX01 or CC-PAIX02 module approved for the engineered system.
Analog channels
Terminate up to 16 supported analog-input channels according to the IOTA and IOM wiring instructions.
Field conductors
Series C field connectors accept up to 12 AWG / 2.5 mm2 stranded wire.
Power distribution
The IOTA receives 24 VDC system power through the Series C bussed-power arrangement.
System interface
The installed IOM communicates over the Series C I/O Link through the carrier and controller architecture.

Installation & Wiring

01 - Verify the exact assembly
Match CC-GAIX11 on the quotation, IOTA label and packaging; do not confuse it with the non-redundant CC-GAIX21.
02 - Confirm the installed IOM
Verify the required HART or non-HART analog-input module and its channel configuration before wiring.
03 - Mount the IOTA
Install the 12-inch redundant IOTA in the approved Series C cabinet and carrier arrangement with required clearance.
04 - Land field wiring
Use the documented terminal assignments and maintain the required intrinsic-safety segregation and grounding.
05 - Commission channels
Check channel type, range, HART requirement, open-wire diagnostics and redundancy in the Experion configuration.

Operation & Maintenance

Ambient temperature
Series C general internal cabinet operating limit is 0 to +60 degrees C.
Storage
Series C general transportation and storage temperature limit is -40 to +85 degrees C.
Humidity
5 to 95% relative humidity, non-condensing.
Enclosure rating
Series C general rating is IP20 / NEMA 1 and requires suitable cabinet installation.
Corrosion class
The CC prefix denotes coated hardware for ISA S71.04 G3 environments.
Approvals
Series C platform documentation lists FM, CSA, ATEX, IECEx and CE compliance subject to the documented model and installation conditions.

FAQ

Q1. How can a quotation be verified as the exact CC-GAIX11 model?
Match CC-GAIX11 on the quotation, IOTA nameplate and packaging. The official item is a 12-inch redundant IS analog-input IOTA, not a CC-PAIH or CC-PAIX electronic module and not the CC-GAIX21 non-redundant IOTA.
Q2. How can New, Used or Refurbished condition be distinguished for CC-GAIX11?
Request date-marked photos of the complete label, terminal blocks, IOM connectors, carrier contacts, redundant positions and packaging. Look for landed-wire marks, terminal damage, corrosion, replaced labels or repaired plastic.
Q3. How should supplier legality and reliability be checked?
Verify the supplier legal entity, physical address, payment beneficiary and traceable contact. The written offer should state Honeywell CC-GAIX11, redundant analog-input IOTA, condition and quantity.
Q4. Which engineering details must be checked before purchase?
Confirm the supported CC-PAIH or CC-PAIX IOM, HART requirement, 16-channel signal plan, intrinsic-safety design, redundant architecture, 12-inch cabinet space and Series C system compatibility.
Q5. What physical evidence should be requested before payment?
Ask for one current photo set showing the full CC-GAIX11 label, terminal blocks, both IOM connector areas, bussed-power interface, mounting hardware and exact offered quantity.
Q6. Can CC-GAIX21 or CC-TAIX11 replace CC-GAIX11?
Not automatically. CC-GAIX21 is the non-redundant IS IOTA, while CC-TAIX11 is a different redundant analog-input IOTA option. Match redundancy, intrinsic-safety requirements, IOM compatibility and full model before substitution.

Recommend Models

BC-ATS-151510
CLV430-6010
GLF6101SM4S
1616 K10
870-523/281-581
3RV1021-1HA10
17HS8401SY-DP
02250125-861
HW2L-M1F10QD-S-24V
RJ45SC RJ45SC 841-5M
TK-0N 4NK0AL
MX150
WMZS2D25
100-24E
STR82D-22E02J0-GFAGG00A0-A-CDC
92125A128 35-725001-004
IPM8-A6-FWL-20
MAI32LAD 001-1113-05-01
RT1694/0-27
44B-AAA-GDDA-1KB9
102D
VMPA2-FB-EMG-4
TLS0022M
WMZH2C15
CVR-RH-60100
OSS-1590-101-C
700-HB32Z12
A03B-0815-C003
WMZT1D01T
KGHL161
3500/53 PWA:133388-01P
SKF 6210 2RSJEM
F8576
ABB PP880R 3BSE069295R1
6422482G7
CNMA120416 TP100
Notifier ID3000
45UV5-1010
GC-1CC0
1400-2-M
ABB REC670 1MRK004814
A6488TML-1/32
E4408B ESA-L
TB20H100
S23-12734
SCT-1250-100
33-9860
EBAI-B3.125-.5C-1.5EC
FAD4LW5043
3LD9221-0A
2910-3014-00
NR-2012-PM
2001-333
NAC-16-472-D
1734-ARM
CF3-G8-AB
Ti400
100-C16D10
TK-5-1N 7-11A
5201KDD

Get a Free Quote

Our representative will contact you soon.
Email
Name
Mobile
Company Name
Message
0/1000

Get a Free Quote

Our representative will contact you soon.
Email
Name
Mobile
Company Name
Message
0/1000