Siemens 6DL1135-6TF00-0PH1 ET 200SP HA HART Output Module

Product Name: SIMATIC ET 200SP HA AQ 8xI HART Analog Output Module
Brand Name: Siemens
Model Number: 6DL1135-6TF00-0PH1
Place of Origin: Germany
Warranty: 12 Months
Whatsapp: +86 180 2077 6782
Email: [email protected]

Appurtenance:
  • Overview
  • HART Integration
  • Channel Diagnostics
  • Specifications
  • Purchase
  • FAQ
  • Other Products
  • Recommended Products
Eight-channel HART current-output module for highly available process automation
The AQ 8xI HART HA module provides eight 16-bit current outputs with channel diagnostics, HART communication and reparameterization in RUN. Terminal-block selection, load resistance, output range, HART engineering and redundancy configuration must be verified for the actual ET 200SP HA station.
Process I/O match: Confirm the exact module code, terminal-block type, channel ranges, HART device assignments, redundancy partner, PCS 7 or TIA engineering version and the safe condition of every connected actuator before replacement.

HART Integration

6DL1135-6TF00-0PH1 is the SIMATIC ET 200SP HA AQ 8xI HART HA analog output module. It supports eight current outputs, HART Rev. 5 to 7 communication, channel diagnostics and I&M data for process-control maintenance.
The module can be reparameterized in RUN and supports redundancy with the approved M1 terminal-block arrangement. These functions depend on the station design and cannot be inferred from the module label alone.
Channel range, loop load and HART assignment must agree with the connected field actuator and control-system project.
Loop range
Verify each channel is configured for the intended 0-10, 0-20 or 4-20 mA range before connecting the actuator.
HART devices
Record the device tag, address, variables and diagnostic status for every loop before moving wiring or replacing the module.
Terminal block
Match the installed H1, M1, N0, H0 or M0 terminal-block arrangement and its redundancy role; do not select by color alone.

Channel Diagnostics

Use channel and HART diagnostics to separate configuration faults from wiring, load and field-device problems.
No output current
Check channel enable, configured range, wire continuity, actuator polarity, load resistance and supply voltage before exchanging hardware.
HART unavailable
Confirm the 4-20 mA HART range, supported device revision, loop impedance and engineering assignment, then read the channel diagnostics.
Redundant channel
Compare both module states and the M1 redundancy configuration before removing either partner from a running station.

Specifications

Product type designation
AQ 8xI HART HA
Order number
6DL1135-6TF00-0PH1
Firmware version
V1.0; firmware update possible
Analog outputs
8 current outputs
Output ranges
0-10, 0-20 and 4-20 mA
Resolution
Up to 16 bit including sign
Accuracy
Plus or minus 0.1%
HART support
Revision 5 to 7
Terminal blocks
H1, M1, N0, H0 and M0
Redundancy
Supported with approved M1 arrangement
Supply voltage
24 V DC; 19.2 to 28.8 V DC
Engineering
TIA V16; STEP 7 V5.6; PCS 7 V9.0

Purchase

Quotation
Current price and availability
Payment
T/T or agreed terms
Lead time
Confirmed with quotation
Shipping
DHL, FedEx, UPS or agreed freight
Warranty
12 months

FAQ

Q1
How should an engineer confirm terminal-block compatibility for 6DL1135-6TF00-0PH1 before purchase?
Identify the installed terminal block and station design, not only the CC00 color code. Compare the H1, M1, N0, H0 or M0 type, channel wiring, redundancy arrangement and the hardware configuration in PCS 7, STEP 7 or TIA Portal.
Q2
Why can a channel on 6DL1135-6TF00-0PH1 show a valid configured value but deliver no output current?
Check that the channel is enabled and assigned to the correct current range, then measure loop continuity, actuator polarity and load resistance. Review wire-break, short-circuit, underflow and overflow diagnostics before replacing the module.
Q3
What should be checked when HART communication fails on 6DL1135-6TF00-0PH1 but the 4-20 mA signal still works?
Verify that the channel uses the HART-capable range, the field device supports HART Rev. 5 to 7, loop impedance is suitable and the correct device is assigned in engineering. Read the channel and HART status for a wiring or command error.
Q4
Can 6DL1135-6TF00-0PH1 be exchanged in a redundant ET 200SP HA configuration without stopping the process?
Only when the approved M1 redundancy design, station state and plant procedure permit it. Confirm which partner is active, place the process in a controlled condition, verify bumpless behavior and monitor both module diagnostics throughout the exchange.
Q5
How should output scaling be verified after installing 6DL1135-6TF00-0PH1?
Force or command safe test values under the plant procedure and compare the engineering raw value, measured loop current and actuator response at several points. Confirm the configured range and limits before releasing automatic control.
Q6
What evidence should be saved before reparameterizing 6DL1135-6TF00-0PH1 in RUN?
Archive the station configuration, channel ranges, HART assignments, redundancy status and current diagnostics. Record the safe operating window and verify each affected actuator immediately after the online change.

Other Products

POL95U.00
002640
KS40 - 9404 406 40991
110063001 2RP
PM5300 METSEPM5320
POL635.00
3113A
107-MX
140 CPU 113 02
1SAP450000R0001 AO523
CU351O 100-240V9
PXM20
440R-G23216 MSR142RTP
EY200
ENCL-MZ800-PAN
295619-003
PDT 3100 / STBPDT3100
IQE35-1201U80035
6590 COMP-Y/C
MMX-400 / MMX-1 300
LV540003 CVS400F
CMD5B9102
LNL-1320
WRT-822B
S-532-0 s UNC532
P8-HDMI2-4KDS
GX-7
LBB4442/00
BSAP-2035 17000949F1
M8CS 2C13793G06

Get a Free Quote

Our representative will contact you soon.
Email
Name
Mobile
Company Name
Message
0/1000

Get a Free Quote

Our representative will contact you soon.
Email
Name
Mobile
Company Name
Message
0/1000