siemens 6es7157 0ad82 0xa0-0

SIEMENS

Home >  Products >  SIEMENS

Siemens 6ES7157-0AD82-0XA0 SIMATIC DP/PA Coupler Ex [ia]

Product Name: SIMATIC DP/PA Coupler Ex [ia]
Brand Name: Siemens
Model Number: 6ES7157-0AD82-0XA0
Place of Origin: Germany
Warranty: 12 Months
Whatsapp: +86 18020776782
Appurtenance:
  • Overview
  • PA Integration
  • Description
  • Installation
  • Specifications
  • Commercial Term
  • Contact info
  • FAQ
  • Other Products
  • Recommended Products
Intrinsically safe PROFIBUS PA coupling for hazardous-area field instrumentation
The Siemens DP/PA Coupler Ex [ia] connects a PROFIBUS DP segment to a 31.25 kbit/s PROFIBUS PA segment while supplying up to 110 mA for approved PA field devices. It is intended for process installations that require FISCO-compatible intrinsic safety.
Segment engineering check: Confirm product state 02 or later, 24 V DC SELV supply, PA current budget, field-device intrinsic-safety data, hazardous-area approvals, bus length, shield bonding and segment termination before purchase.

PA Integration

The coupler must be engineered together with the complete PA segment and its intrinsic-safety documentation.
Current budget
Add the operating current of every field device and include cable losses and approved reserve; the coupler output is limited to 110 mA.
Bus design
Verify trunk and spur lengths, two valid terminators, shield continuity and the 31.25 kbit/s PA topology before commissioning.
Safety parameters
Confirm that every PA device and cable satisfies the official Li, Ci, Ui and Ii limits and the selected FISCO or entity concept.

Description

6ES7157-0AD82-0XA0 converts the DP transmission rate to the PROFIBUS PA rate and provides galvanic isolation between the 24 V supply, PROFIBUS DP and PROFIBUS PA interfaces. The official product information permits up to 31 PA field devices when the current and safety limits are satisfied.
A replacement must be reviewed as part of the complete intrinsically safe segment. Record the connected field devices, cable parameters, spur layout, terminators, supply voltage, enclosure conditions and product-state label before removing the installed coupler.

Installation

Hazardous-area service requires controlled installation, grounding and documentation rather than a simple like-for-like visual exchange.
Supply and isolation
Use the specified 24 V DC SELV source and preserve the required electrical separation from the non-intrinsically safe DP side.
Mechanical review
Check enclosure protection, ventilation, mounting clearance, strain relief and terminal condition before energizing the replacement.
Acceptance test
Verify DP communication, PA segment voltage, field-device visibility and diagnostics before returning the process loop to service.

Specifications

Product type designation SIMATIC DP/PA Coupler Ex [ia]
Order number 6ES7157-0AD82-0XA0
Primary function PROFIBUS DP to PROFIBUS PA coupling
PA transmission rate 31.25 kbit/s
PA output voltage Typically 13.5 V DC
PA output current Maximum 110 mA
Supply voltage 24 V DC from a SELV source
Connected PA devices Up to 31, subject to current and safety limits
Degree of protection IP20
Operating temperature -25 to +60 degrees C
Dimensions 80 x 125 x 130 mm
Net weight Approximately 550 g

Commercial Term

Quotation
Current price and availability
Payment
T/T or agreed terms
Lead time
Confirmed with quotation
Shipping
DHL, FedEx, UPS or agreed freight
Warranty
12 months

Contact info

FAQ

Q1
Can 6ES7157-0AD82-0XA0 replace an older 6ES7157-0AD00-0XA0 without revalidating the PA loop?
No. The newer coupler has an intrinsic-safety short-circuit current of 247 mA instead of 215 mA. Older field devices or loop approvals may be limited to 215 mA, so the FISCO or entity calculation and the plant safety dossier must be approved again before substitution.
Q2
Where must 6ES7157-0AD82-0XA0 be positioned in a PROFIBUS PA segment?
Install it at the beginning or the end of the PA segment. Its internal PA bus terminator cannot be switched off, so placing it in the middle can create an extra termination and cause low signal amplitude or intermittent device loss.
Q3
How many PA field devices can 6ES7157-0AD82-0XA0 actually power from its 110 mA output?
The catalogue limit of 31 devices is not the working design limit for every loop. Add the normal current of each device, cable loss and an engineering reserve, then confirm that the total stays below 110 mA and that every Li, Ci, Ui, Ii and Pi value remains within the approved intrinsic-safety calculation.
Q4
Can 6ES7157-0AD82-0XA0 be mounted directly in Zone 1 or Zone 21?
Do not treat the module and the PA field circuit as having the same installation permission. The coupler is a category 3G PROFIBUS node for Zone 2 or a safe area; installation for dust zones requires an enclosure certified for the applicable zone, while the intrinsically safe PA circuit may extend to approved field equipment in Zone 0 or Zone 20.
Q5
Why does 6ES7157-0AD82-0XA0 show DP activity while every PA instrument is offline?
Use the ON, DP and PA indications to separate supply, DP-side and PA-side faults. If ON and DP are active but PA is not, measure the PA output, confirm polarity, one valid termination at the far end, cable continuity and the 110 mA load before changing the coupler.
Q6
May I connect a commissioning tool or another DP device to 6ES7157-0AD82-0XA0 while it operates with an IM 157?
No. In that operating mode the DP interface is permitted only for passive bus monitoring. Siemens does not permit parameterization equipment or an additional DP device on that interface, so commissioning must use the approved system path rather than the coupler port.

Other Products

RVP26
ABB 2CDG110133R0011
DDNI485
QBM3020-5 S55720-S236
ABB S800 TU830V1 3BSE013234R1
DIN-8SW8
01DGBP-E2CRS
318312
ADV551-P13
inbio460
DLP-PU/E
ABB 1KGT033100R0001 520AID01
ABB S800 I/O TU830V1 3BSE013234R1
WLC316R
310 04.56.00.50.00
PC4416 CDC-623 H-7PCRDIO73B
PL-1381-11-V
F088
KJ1502X1-BD1
ABB CM577-ETH 1SAP170700R0001
Altronix WayPointEAV
1000 9611
Alpha2 800-001-2000
6ES7648-6CA05-0YX0
EC3-X33
ABB NRFC-41 57619651
KPDL400
6EV5000-1BC
C-Bus2 L5504RVFC
OCM-DPR-85-PD-ST-ACV

Get a Free Quote

Our representative will contact you soon.
Email
Name
Mobile
Company Name
Message
0/1000

Get a Free Quote

Our representative will contact you soon.
Email
Name
Mobile
Company Name
Message
0/1000