INPUTS
2 digital inputs
|
RATED VOLTAGE
24 V DC
|
|
INPUT STANDARD
IEC 61131 Type 1
|
MODULE SIZE
10 × 64 × 51 mm
|
|
LEAD TIME
In stock
|
WARRANTY
1 year
|
Discrete signal acquisition
Provides two 24 V DC digital input channels for detecting binary field states in a SIMATIC SC installation.
|
Two-wire sensor connection
The official data sheet permits connectable two-wire sensors with a maximum permissible quiescent current of 1.5 mA.
|
Long field wiring
Specified cable lengths reach 1000 m with shielded cable and 600 m with unshielded cable.
|
Legacy system maintenance
Supports model-specific repair and replacement work in installed ET 200L-SC / SIMATIC SC systems.
|
|
Complete model
|
6ES7121-1BB00-0AA0
|
|
Brand
|
Siemens
|
|
Product family
|
SIMATIC SC / ET 200L-SC
|
|
Product type
|
Electronic submodule with digital inputs
|
|
Digital inputs
|
2
|
|
Rated supply and input voltage
|
24 V DC
|
|
Input characteristic
|
IEC 61131, Type 1
|
|
Signal 0 voltage
|
-3 to +5 V DC
|
|
Signal 1 voltage
|
13 to 30 V DC
|
|
Input current at signal 1
|
Typically 7 mA
|
|
Input delay, 0 to 1
|
1.2 to 4.8 ms
|
|
Input delay, 1 to 0
|
1.2 ms to 4.8 µs, as stated in the official data sheet
|
|
Required terminal block
|
TB16SC
|
|
Required slots
|
1 of 8
|
|
Power loss
|
Typically 0.4 W
|
|
Shielded cable length
|
Up to 1000 m
|
|
Unshielded cable length
|
Up to 600 m
|
|
Isolation test voltage
|
1500 V AC
|
|
Diagnostics and alarms
|
Not provided
|
|
Dimensions
|
10 × 64 × 51 mm (W × H × D)
|
|
Weight
|
Approximately 15 g
|
|
Lifecycle
|
Spare part; product deleted without replacement
|
|
Discrete signal acquisition
Provides two 24 V DC digital input channels for detecting binary field states in a SIMATIC SC installation.
|
|
Two-wire sensor connection
The official data sheet permits connectable two-wire sensors with a maximum permissible quiescent current of 1.5 mA.
|
|
Long field wiring
Specified cable lengths reach 1000 m with shielded cable and 600 m with unshielded cable.
|
|
Legacy system maintenance
Supports model-specific repair and replacement work in installed ET 200L-SC / SIMATIC SC systems.
|
|
Module format
|
Single-width electronic submodule
|
|
Terminal interface
|
Requires TB16SC terminal block
|
|
Input channels
|
2 non-isolated digital inputs
|
|
Backplane relationship
|
No channel-to-backplane potential separation; optocoupler stated
|
|
Status indication
|
Green status indicator for each digital input
|
|
Package statement
|
8 pieces per packaging unit
|
|
1 · Confirm the base
Verify that the installed station uses the TB16SC terminal block and has one free single-width slot.
|
|
2 · Check field voltage
Confirm 24 V DC signals and the official signal 0 and signal 1 voltage ranges before wiring.
|
|
3 · Match sensors
For two-wire sensors, verify that the permissible quiescent current does not exceed 1.5 mA.
|
|
4 · Observe cable limits
Use the stated maximum lengths for shielded and unshielded input wiring.
|
|
5 · Test the channel
After installation, verify the green input-status indication and the PLC input image for both channels.
|
|
Required base
The electronic submodule requires the Siemens TB16SC terminal block.
|
|
Slot demand
One single-width slot is required in the eight-slot hardware arrangement.
|
|
Electrical fit
Field devices must match the 24 V DC Type 1 input characteristic and signal thresholds.
|
|
Lifecycle check
The model is discontinued without a Siemens replacement; legacy-system identification is essential.
|
|
Q1 · How is the exact quoted module verified?
Match 6ES7121-1BB00-0AA0 on the label and quotation, and confirm that the description states two 24 V DC digital inputs rather than a digital-output or analog submodule.
|
|
Q2 · How can New, Used or Refurbished condition be distinguished?
Request current close-up photos of the label, connector edge, housing and status-LED area. Look for insertion marks, repaired plastic, oxidation or removed identification.
|
|
Q3 · How should the supplier be qualified?
Verify the legal company identity, payment beneficiary, traceable offer and ability to provide the official Siemens two-page data sheet for the exact discontinued part.
|
|
Q4 · What must engineering check before ordering?
Confirm the TB16SC base, one available slot, 24 V DC Type 1 signals, two required inputs, sensor quiescent current and permitted cable length.
|
|
Q5 · What evidence should be obtained before payment?
Ask for dated photos showing the complete part number, packaging quantity, connector edge and both input-channel indicators, linked to the same quotation.
|
|
Q6 · Can another SIMATIC SC submodule replace it?
Not automatically. Input/output function, channel count, voltage characteristic, terminal-block requirement and slot format must all match the original design.
|
|
AV5115DNv1
|
161878 KM PPE-5
|
TP04-1141-5NN
|
|
APIN0304 019FYT
|
SNC-ZM550
|
E12-948-452 MS-A30VD-K1
|
|
ABB UMC100 1SAJ530000R1100
|
DVB-T2 MPEG-4
|
MS-Combo-1
|
|
GT5 E9733BA-01
|
Z012.041A/01
|
ABB RXMVB2 RK 251 205-AN
|
|
7012AC 1423157-5
|
CFQ-5251
|
AT-MC102XL-40 990-000445-40
|
|
ZE544-001A-521
|
RA1483A
|
1RK 221 052-AS
|
|
ABB RVT12-1/5A 2GCA289005A0050
|
RH86P
|
SSB401-53
|
|
SF61B
|
140-112EX
|
F088
|
|
AV5155DN
|
ABB 2CDG 110 094 R0011
|
CLV422-0010
|
|
PWFMDB100
|
40071 61055 Z1005.H
|
D-1101-RSG2100 RJ45TX01
|
|
LOP5B-2
|
800T-FX6D2
|
DMX512
|
|
PWM-PK-3
|
ABB SA/S 8.6.1 /2CDG 110 037 R0011
|
ENCL-MZ800-PAN
|
|
6FL7820-8CB10 AFI5100
|
ASD-A2-0121-U
|
GE IC3600SSLB1G
|
|
350-251-10 MHN1-25MB
|
GV3P40
|
AR-133
|
|
416861G 416851G
|
ELRV-30/Z89
|
GHQ631 0062 R0111
|
|
GT5 AS E9733BA-01
|
0-500V
|
X216 216-0BA00-2AA3
|
|
9425/199019B-02L
|
AVPR100S151213
|
DDI161 05-006-161 DKL011
|
|
UA-25EX
|
DSL-322
|
ABB 2CDG006132R0313/R0314
|
|
3EM17860BTBV
|
NFSB100-S00
|
9407 489 60001 KS800-CAN
|
|
SK41-32
|
MTL4015
|
Extech 407910
|