ABB AC500 S500 AO523 16-Channel Analog Output Module | Original New

ABB AC500 S500
AO523
16-Channel Analog Output Module
16 AO | 8 configurable U/I plus 8 voltage outputs | -10 to +10 V, 0 to 20 mA, 4 to 20 mA | 12 bits including sign | Order code 1SAP250200R0001
LEAD TIME: In stock   |   WARRANTY: 1 year
Appurtenance:
  • Overview
  • Technical Data
  • Inquiry
  • Applications
  • Measurement
  • Installation
  • Diagnostics
  • FAQ
  • Recommend Models
  • Recommended Products
ABB AC500 S500
AO523 16-Channel Analog Output Module
Exact order code: 1SAP250200R0001
OFFICIAL PRODUCT DESCRIPTION
Analog output module with 16 outputs in two groups: eight channels configurable for voltage or current and eight additional voltage-output channels.
PRIMARY ENGINEERING VALUE
One S500 module delivers 16 analog outputs with 12-bit conversion including sign, channel indication and module-wise isolation.

Technical Data

OFFICIAL PRODUCT DATA
Technical Data
ABB hardware manual 3ADR010121, revision 26
Complete model
AO523
Brand
ABB
Product family
AC500 / S500
Product type
16-channel analog output module
Order code
1SAP250200R0001
Analog outputs
16 channels in two groups; 8 voltage/current channels and 8 voltage channels
Output ranges
-10 to +10 V; 0 to 20 mA; 4 to 20 mA
Resolution
12 bits including sign
Process voltage
24 V DC
Current consumption
Approx. 2 mA logic supply; typical 0.075 A no-load process current
Settling time
Typical 5 ms for a full-range change with resistive load
Voltage output load
Maximum +/-10 mA
Current output load
0 to 500 ohm including cable resistance
Accuracy
Voltage output typical +/-0.5% full scale and maximum +/-1% full scale from 0 to 60 deg C
Isolation
Module-wise galvanic isolation from I/O bus
Protection
Reverse polarity, reverse supply, short circuit and temporary overvoltage protection up to 30 V DC
Terminal unit
TU515 or TU516
Mounting
DIN rail; horizontal or vertical according to AC500 system limits
Dimensions
67.5 x 135 x 84.5 mm maximum width x height x depth
Weight
300 g
Lifecycle
Active

Inquiry

DIRECT CONTACT
Inquiry
Product-specific inquiry for AO523
CONTACT
STELLA

Applications

APPLICATION PROFILE
Applications
Supported use cases for AO523
Voltage actuation
Use all 16 channels for -10 to +10 V control signals to drives, positioners or analog actuators.
Current actuation
Configure up to eight designated channels for 0 to 20 mA or 4 to 20 mA current loops.
Mixed signaling
Combine current and voltage outputs within the supported channel-group architecture.
Dense control
Provide sixteen analog setpoints from one S500 module to reduce panel footprint.

Measurement

SIGNAL AND CHANNEL BEHAVIOR
Measurement
Configuration and conversion characteristics for AO523
Channel groups
Outputs are organized in two groups; each group contains four U/I channels and four voltage-only channels.
Digital conversion
The module uses 12-bit conversion including sign for bipolar voltage operation.
Load limits
Voltage channels supply up to +/-10 mA; current loops support a total load of 0 to 500 ohm.
Settling
Typical settling time for a full-range change with resistive load is 5 ms.

Installation

MOUNTING AND WIRING
Installation
Installation requirements for AO523
Terminal unit
Install on ABB TU515 screw or TU516 spring terminal unit.
Supply
Provide 24 V DC process voltage and use the specified terminal-unit fuse arrangement.
Wiring
Use shielded cable and keep the current-loop burden, including conductor resistance, within 500 ohm.
Mounting envelope
Allow 67.5 mm width, 135 mm height and 84.5 mm maximum depth with unobstructed natural convection.

Diagnostics

CHANNEL SUPERVISION
Diagnostics
Status indication and protective behavior for AO523
Channel indication
Sixteen yellow LEDs indicate output-channel states and follow the analog signal level.
Module indication
A green LED indicates process supply while red channel-group LEDs report faults.
Output diagnostics
Current wire break and voltage short-circuit conditions are reported for applicable output levels.
Electrical protection
Outputs are protected against reverse polarity, reverse supply, short circuit and temporary overvoltage up to 30 V DC.

FAQ

PROCUREMENT AND ENGINEERING CHECKS
FAQ
Six questions specific to ABB AO523 and order code 1SAP250200R0001
Q1. How can a buyer confirm the quoted unit is exactly AO523?
Match AO523 and complete order code 1SAP250200R0001 on the label, quotation and ABB documentation. Confirm 16 outputs, eight current-capable channels and 12-bit conversion including sign.
Q2. How can New, Used or Refurbished condition be distinguished?
Request dated images of the ABB packaging, front label, output terminals, I/O-bus contacts, locking features and housing. Require written disclosure of previous installation, repair or component replacement.
Q3. How should the supplier be verified before procurement?
Confirm the legal company name, registered address, payment beneficiary and traceable ABB supply history. The quotation must state AO523, 1SAP250200R0001, offered condition and terminal-unit scope.
Q4. Which specifications should engineers verify before purchase?
Verify 24 V DC supply, 16 outputs, which eight channels support current, required voltage/current ranges, 12-bit resolution, TU515 or TU516 terminal unit, 67.5 x 135 x 84.5 mm envelope and load limits.
Q5. What physical evidence should be required before payment?
Require shipment-specific photos or video showing AO523, 1SAP250200R0001, terminal interface, I/O-bus contacts, LEDs, housing condition and a dated purchase-order reference.
Q6. Can another analog output module replace AO523?
Not automatically. Other modules can differ in current-capable channel count, signal range, load limit, resolution, isolation, wiring and terminal-unit compatibility. Approve only after exact engineering comparison.

Recommend Models

RANDOM MIXED-BRAND SELECTION
Recommend Models
Independent 60-model selection for AO523
369B1860G0016
1X01177H01
NTHS03
KJ3243X1-BB2
SPHSS13
6DR5020
CE4100
EJA110E-JM4G-917DB/NF2
1C31199G05
SE4003S5B1
EJA110E-JMS
SPDSI14
sipos7
5X00226G04
IMAS23
5X00106G02
mai50
369B1842G001
5DR5020-0EG01-0A
1C31192G01
SPICT13A
6ES7331-1KF02
KC3020X1-BA1
INNPM22
BRC300/SPBRC300
5X00500G01/1X00691H01
KJ3245X1-BK1
KJ2005X1-BK1
KL4502X1-PA1
DHF-504B
1C31234G01
PR6423/00R-010
SE6505T01
OC6000
IMSED01
INNPM12
VE5129
KJ1611X1-GB1
5X003
369B
SPFEC12/FEC12/IMFEC12
5X00784G01
5X00481G04
VI702
KC4011X1-BP1
KJ2006X1-BM1
SE4033S2B1
KJ3223X1-BA1
DSI22
SPASO11
CE4002S1T2B8
3051DP2A62A
INNIS21
1C31238H
SPIIT1
DSQC-328
1C31166G02/1C31169G02
KJ1611X1-BA1
1C31194G03
MAI5MAO50MD

Get a Free Quote

Our representative will contact you soon.
Email
Name
Mobile
Company Name
Message
0/1000

Get a Free Quote

Our representative will contact you soon.
Email
Name
Mobile
Company Name
Message
0/1000