allen bradley controllogix 1756 1756 it6i 6 point isolated thermocouple input module-0

ROCKWELL

Home >  Products >  ROCKWELL

Allen-Bradley ControlLogix 1756 1756-IT6I 6-Point Isolated Thermocouple/mV Input Module | Original New

Allen-Bradley ControlLogix 1756 6-Point Isolated Thermocouple/mV Input Module
Complete Model
1756-IT6I
Official Product Description
ControlLogix temperature-sensing analog input module with six individually isolated thermocouple or millivolt channels, one cold-junction sensor and two selectable millivolt ranges.
CORE FEATURE: Six individually isolated thermocouple channels with ITS-90 linearization and selectable standard or high-resolution millivolt ranges.
LEAD TIME: In stock
WARRANTY: 1 year
Appurtenance:
  • Overview
  • Technical Data
  • Inquiry
  • Features
  • Wiring
  • Installation
  • Environment
  • FAQ
  • Recommend Models
  • Recommended Products
Product Overview
1756-IT6I is an Allen-Bradley ControlLogix 1756 temperature-sensing analog input module with six individually isolated thermocouple channels and one cold-junction sensor.
Rockwell Automation specifies -12 to 78 mV and -12 to 30 mV input ranges with 16-bit conversion and support for B, E, J, K, R, S, T, N, C, D and L thermocouple types.
The module provides ITS-90 thermocouple linearization, open-circuit detection, selectable notch filtering and one ControlLogix chassis slot.

Technical Data

Complete model
1756-IT6I
Brand
Allen-Bradley / Rockwell Automation
Product family
ControlLogix 1756
Product type
Individually isolated thermocouple and millivolt input module
Inputs
6 individually isolated thermocouple channels and 1 cold-junction sensor
Input ranges
-12 to 78 mV; -12 to 30 mV high-resolution range
Resolution
16 bits; 1.4 uV/bit typical or 0.7 uV/bit high-resolution
Thermocouple types
B, E, J, K, R, S, T, N, C, D and L (TXK/XK)
Linearization
ITS-90
Current draw at 5.1 V
250 mA
Current draw at 24 V
125 mA
Total backplane power
4.3 W
Power dissipation
4.3 W maximum
Input impedance
More than 10 MOhm
Open-circuit detection
Positive full-scale indication within 2 seconds
Overvoltage protection
120 VAC/DC maximum
Channel bandwidth
15 Hz at -3 dB, notch-filter dependent
Settling time
Less than 80 ms to 5 percent of full scale
Calibrated accuracy at 25 degrees C
Better than 0.1 percent of range
Isolation voltage
250 V continuous, channels-to-backplane and channel-to-channel
Removable terminal block
1756-TBNH or 1756-TBSH, ordered separately
Dimensions
144.5 x 34.6 x 146.9 mm, height x width x depth
Weight
Approximately 0.2 kg (0.5 lb)
Slot width
One ControlLogix chassis slot
Enclosure type
None, open-style equipment
Operating temperature
0 to 60 degrees C
Storage temperature
-40 to +85 degrees C
Relative humidity
5 to 95 percent, noncondensing
Lifecycle
Discontinued March 31, 2017
Official sources
Rockwell Automation product page; publication 1756-TD002M-EN-E pages 110-113; official drawing ABIOM091; Rockwell ControlLogix 1756 system reference

Inquiry

Features

Individually isolated channels
Six thermocouple or millivolt inputs are isolated channel-to-channel and from the ControlLogix backplane.
Broad thermocouple support
The published list covers eleven thermocouple designations with ITS-90 linearization.
High-resolution option
Select the -12 to 30 mV range for nominal 0.7 uV/bit resolution.
Cold-junction measurement
One supplied cold-junction sensor supports thermocouple reference compensation at the 20-pin RTB.

Wiring

Field wiring
Use a 1756-TBNH or 1756-TBSH 20-pin removable terminal block housing; order the RTB separately.
Thermocouple channels
Connect IN-0 through IN-5 and their returns with polarity and shield treatment shown in the official diagram.
Cold-junction sensor
Install the specified CJC sensor across the published CJC positive and negative terminals.
Backplane
The module draws 250 mA at 5.1 V and 125 mA at 24 V from the ControlLogix backplane.

Installation

01 - Verify the complete catalog number
Match 1756-IT6I on the quotation, module label, packaging and Rockwell Automation discontinued-product record.
02 - Confirm the thermocouple
Verify the type, polarity, temperature span and required -12 to 78 mV or -12 to 30 mV range.
03 - Select the RTB and CJC
Use 1756-TBNH or 1756-TBSH and confirm the correct cold-junction sensor and terminal placement.
04 - Wire isolated channels
Follow the official 20-pin diagram, maintain shield grounding and do not defeat the 250 V isolation arrangement.
05 - Configure and calibrate
Set the thermocouple type, units, range, notch filter and scaling, then complete the specified calibration checks.

Environment

Operating temperature
0 to 60 degrees C.
Storage temperature
-40 to +85 degrees C.
Relative humidity
5 to 95 percent, noncondensing.
Mechanical endurance
2 g vibration at 10-500 Hz, 30 g operating shock and 50 g nonoperating shock.
Protection
Open-style equipment; install the module in a suitable industrial enclosure.
Certifications
UL, CSA, CE, RCM, ATEX, FM, KC and EAC when marked.
Lifecycle
Discontinued; verify replacement and software migration requirements before purchase.

FAQ

Q1. How can the exact quoted 1756-IT6I be verified?
Match 1756-IT6I on the quotation, module label and packaging. Confirm six isolated thermocouple channels, one CJC, the -12 to 78 mV and -12 to 30 mV ranges and the 20-pin RTB interface.
Q2. How can New, Used or Refurbished condition be distinguished?
Request date-marked photos of the full label, serial and series markings, CAL and OK indicators, CJC sensor, RTB connector, backplane connector and housing. Check for changed labels, worn terminals, repaired plastic or prior panel residue.
Q3. How should supplier legality and reliability be checked?
Verify the supplier legal entity, registered address, invoice details, payment beneficiary and traceable contact. The offer must state Allen-Bradley, 1756-IT6I, discontinued status, condition, quantity and whether the CJC and RTB are included.
Q4. Which specifications must engineering confirm before purchase?
Confirm thermocouple type and polarity, -12 to 78 mV or -12 to 30 mV range, 16-bit resolution, one-CJC arrangement, 250 V isolation, 1756-TBNH or 1756-TBSH RTB, backplane power and controller software profile.
Q5. What physical evidence should be requested before payment?
Ask for date-marked photos showing the full 1756-IT6I label, serial and series markings, six-channel analog faceplate, supplied CJC, 20-pin RTB connector, backplane connector, housing condition and packaging.
Q6. Can 1756-IT6I2 or 1756-IRT8I replace 1756-IT6I?
Not automatically. The enhanced and combined RTD/thermocouple modules differ in channel count, CJC arrangement, isolation performance, RTB and software profile. Complete a wiring and program migration review before substitution.

Recommend Models

52421-1000
607429-3
EBM45A-015A-02
NDLPR-164C
100-C09E*10
LC1D25BD
P2S-EA162D25AT
V61R517A-A213JB
STD830-H2HS6AS-1-A-ADE-11S-A-10A0-00-0000
032F1204
0LR0453
VIB5.600
CL05A475MQ5NRNC
LD9000
VFR5100-5FZB
52BJK
BC-ATS-151510
LRD35
3LD9221-0A
GCX1380-22
GV2-RS03
6311 2ZJEM
17HS8401SY-DP
ibaPADU-S-CM
NAC-16-472-D
MT31.DK1ADNBX
KN-DG12
FAZ-C2/1-NA
GE VME-7807RC-412000-350-93007807-412000G
SL-SW1050
NSYTRAC22
CPX-AB-4-M12X2-5POL
VMPA2-FB-EMG-4
51961-39
108 641809 + RAE 3130328
FH-60XT
3RT1017-1AF01
48ASE1M20
ABB 881023-BB RXTUG-21H
GH2BZ-S
81.000.6120.0
VUVG-LK14-B52-T-G18-1H2L-S
SCP451-51-S1
E3S-2LE41
E710 12-0418
WD1001FALS-41Y6A1 - 1TB
B6-30-10
136634-0010-01
SMB100A
RDMC5000
VX3134V-02-5G1
A03B-0815-C001
2000-5420/1399-987
TK0N-0.95 TR13EW-L
DILM12-10 XTCE012B10AD
F8576
R501AY428501001
T22JCC-1
H596-130 250-3000PSIG
5SY6201-7

Get a Free Quote

Our representative will contact you soon.
Email
Name
Mobile
Company Name
Message
0/1000

Get a Free Quote

Our representative will contact you soon.
Email
Name
Mobile
Company Name
Message
0/1000