DIRECT SALES DESK
One point of contact for quotation, delivery and order support.
|
Sales | Phone/Whatsapp | |
|---|---|---|---|
| Jim Pei | [email protected] | +86 18020776782 |
| Model | T8431C |
| Input architecture | Triple Modular Redundant (TMR) |
| Number of inputs | 40 |
| Input signal | 4-20 mA |
| Supported field device type | Sourcing input devices |
| Conformal coating | Yes |
| Backplane supply voltage | 20 to 32 V DC |
| Power | 20 W |
| Module location | T8100 or T8300 I/O module slot |
| Field common isolation | 50 V reinforced, continuous |
| Field common fault insulation | 250 V basic |
| Isolation type test | 2436 V DC for 60 s |
| Channel-to-channel isolation | No channel-to-channel isolation |
| Fusing | No module fuses |
| FTA input impedance | 250 ohm |
| Module input impedance | 16.967 kohm |
| Input current range | 0 to 22 mA |
| Input voltage range | 0 to 5.5 V DC |
| Input thresholds | Configurable per channel |
| Resolution | 3.906 microampere |
| Safety accuracy | +/-200 microampere |
| Calibration accuracy | +/-0.15% |
| Intrinsic safety interface | External barrier required |
| Line monitoring | Selectable per input channel |
| Impulse withstand | 2500 V opto/galvanic isolation barrier |
| Sequence of Events resolution | 1 ms |
| Timestamp accuracy | +/-10 ms |
| Hot replacement | Companion Slot or SmartSlot |
| Safety certification | IEC 61508 SIL 3 |
| Operating temperature | 0 to +60 degrees C |
| Storage temperature | -25 to +70 degrees C |
| Operating and storage humidity | 10% to 95%, noncondensing |
| Dimensions | 266 x 31 x 303 mm |
| Weight | 1.149 kg |
|
PRODUCT PROFILE
Triple Modular Redundant (TMR)
+ 40 ICS TRIPLEX / TRUSTED SAFETY I/O MODULES
|
T8431C is a conformal-coated Trusted TMR analog input module that interfaces forty sourcing field channels through a 4-20 mA measurement path. Three independent slices process each input, while automatic diagnostics supervise the module and its field connections. Configurable voltage thresholds allow the controller to determine channel state and line-fault status. A 2500 V impulse-withstand isolation barrier separates the field interface from the safety-system electronics. The module also records input state changes through onboard Sequence of Events reporting with 1 ms resolution. T8431C supports high-integrity current inputs in process shutdown, fire and gas, turbine protection and other Trusted safety applications. Selectable line monitoring can identify open- and short-circuit field wiring faults for each channel without applying one setting to the entire module. Front-panel indicators show channel condition, wiring faults, health and Active, Standby or Educated mode. Companion Slot and SmartSlot arrangements allow controlled online replacement when the Trusted system is configured for redundancy. Correct threshold values, field barriers and cable polarization must be confirmed before commissioning. |
|
01 / FIELD CURRENT ACQUISITION
Field current acquisition
Forty sourcing field loops deliver their 4-20 mA signals to the isolated input interface.
|
02 / THREE-SLICE CONVERSION
Three-slice conversion
Each TMR slice measures the channel through its own field-interface circuitry and analog-to-digital conversion path.
|
03 / THRESHOLD AND FAULT EVALUATION
Threshold and fault evaluation
Configured thresholds determine input state while line monitoring distinguishes open and short wiring conditions. Voted channel data, diagnostics and time-stamped state changes are passed to the TMR Processor.
|
|
01 / FORTY SUPERVISED CURRENT CHANNELS
Forty supervised current channels
One module concentrates forty analog input loops while retaining channel-specific line monitoring and status reporting.
|
02 / FAULT-TOLERANT PROCESSING
Fault-tolerant processing
Three isolated processing slices allow the safety system to diagnose a fault without losing the complete input function.
|
|
03 / EVENT CHRONOLOGY SUPPORT
Event chronology support
The 1 ms SOE resolution helps correlate process input transitions during trips and post-event analysis.
|
04 / CONTROLLED ONLINE MAINTENANCE
Controlled online maintenance
Companion Slot and SmartSlot strategies support module replacement while the configured redundant path remains available.
|
| 01 | How does ICS Triplex T8431C distinguish a normal current signal from a field wiring fault? | Each channel uses configurable voltage thresholds, and its selectable line-monitoring function identifies open- or short-circuit field wiring conditions. |
| 02 | Which event-timing data can ICS Triplex T8431C provide after a process trip? | The module records channel state changes with 1 ms SOE resolution and a specified timestamp accuracy of +/-10 ms. |
| 03 | Why can ICS Triplex T8431C tolerate a fault in one internal processing slice? | Its three-slice TMR architecture measures and supervises each input independently so the remaining valid paths can sustain the channel result. |
| 04 | Where is ICS Triplex T8431C installed inside a Trusted controller? | It occupies an I/O module slot in a T8100 or T8300 chassis and connects to the selected field termination arrangement. |
| 05 | When may ICS Triplex T8431C be replaced without taking the Trusted application offline? | Online replacement is supported when the system is engineered with the required Companion Slot or SmartSlot active-and-standby configuration. |
| 06 | What must be added before ICS Triplex T8431C is connected to an intrinsically safe field circuit? | The module is not intrinsically safe by itself, so a correctly selected external intrinsic-safety barrier is required. |