DIRECT SALES DESK
One point of contact for quotation, delivery and order support.
|
Sales | Phone/Whatsapp | |
|---|---|---|---|
| Jim Pei | [email protected] | +86 18020776782 |
| Model | T8451C |
| Output architecture | Triple Modular Redundant (TMR) |
| Number of outputs | 40 |
| Nominal output voltage | 24 V DC |
| Conformal coating | Yes |
| Backplane supply voltage | 20 to 32 V DC |
| System power | 27 W |
| Field supply voltage | 18 to 32 V DC |
| Maximum total current at 50 degrees C | 40 A, limited to 8 A per power group |
| Maximum total current at 60 degrees C | 30 A, limited to 6 A per power group |
| Field power dissipation at 50 degrees C | 128 W at maximum power-group current |
| Field power dissipation at 60 degrees C | 96 W at maximum power-group current |
| Module location | T8100 or T8300 I/O module slot |
| Power-group isolation | 50 V reinforced, continuous between power groups |
| Power-group isolation type test | 1411 V DC for 60 s |
| Field common isolation | 50 V reinforced, continuous at field common |
| Field common fault insulation | 250 V basic |
| Field common isolation type test | 2436 V DC for 60 s |
| Channel-to-channel isolation | None |
| Fusing | Not user serviceable |
| Number of power groups | 5 |
| Channels per power group | 8 |
| Output on-state resistance | 1.6 ohm |
| Continuous current rating | 2 A per channel |
| Minimum on-state load current | 50 mA |
| Current measurement range | 0 to 2.7 A, +/-5% or +/-5 mA |
| Voltage measurement range | 0 to 30 V DC, +/-2 V DC |
| Maximum voltage withstand | -1 to +40 V DC |
| Channel-to-channel crosstalk | Less than 1% |
| Maximum load capacitance | 3000 microfarad |
| Output short-circuit protection | Electronic latching |
| Line monitoring | Automatic per output point |
| Sequence of Events resolution | 1 ms |
| Timestamp accuracy | +/-10 ms |
| Safety certification | IEC 61508 SIL 3 |
| Operating temperature | 0 to +60 degrees C |
| Storage temperature | -25 to +70 degrees C |
| Operating and storage humidity | 10% to 95%, noncondensing |
| Dimensions | 266 x 31 x 303 mm |
| Weight | 1.3 kg |
|
PRODUCT PROFILE
Triple Modular Redundant (TMR)
+ 40 ICS TRIPLEX / TRUSTED SAFETY I/O MODULES
|
T8451C is a conformal-coated Trusted TMR digital output module with forty 24 V DC output points arranged in five isolated power groups. Every channel uses a triplicated, monitored switching structure so the load can remain controlled after a single switch or slice fault. Automatic measurements of output voltage and current determine channel state and support open- and short-circuit diagnostics. Electronic latching short-circuit protection is built into each output, and no external channel fuse is required. Sequence of Events reporting records output changes with 1 ms resolution. T8451C drives shutdown valves, relays, annunciators and other discrete final elements in high-integrity process applications. Three fail-safe switching paths work together, while group fail-safe switches supervise each eight-channel field-supply group. Front-panel indicators expose output status, wiring faults and module operating mode to maintenance personnel. A Companion Slot or SmartSlot arrangement can support controlled online replacement in a correctly engineered Trusted system. Field current, load capacitance and the shared power-group limit must be reviewed for every connected device. |
|
01 / SAFETY COMMAND RECEPTION
Safety command reception
The Trusted processor delivers the requested output state through the fault-tolerant inter-module bus.
|
02 / TRIPLICATED SWITCH CONTROL
Triplicated switch control
Three independently supervised fail-safe switching paths act on each 24 V DC output channel.
|
03 / LOAD ENERGIZATION
Load energization
The voted switching structure supplies the field device within its channel and power-group limits. Voltage, current and line-state measurements return diagnostic and SOE information to the safety application.
|
|
01 / FIVE ISOLATED POWER GROUPS
Five isolated power groups
The forty outputs are divided into five groups of eight, supporting structured field-supply distribution and fault containment.
|
02 / PER-CHANNEL CURRENT PROTECTION
Per-channel current protection
Electronic latching limits a shorted output without requiring a user-replaceable fuse on every channel.
|
|
03 / AUTOMATIC WIRING DIAGNOSTICS
Automatic wiring diagnostics
Onboard voltage and current measurements detect open-load, missing-supply and short-circuit conditions.
|
04 / SINGLE-FAULT OUTPUT CONTINUITY
Single-fault output continuity
The six-element TMR switch arrangement retains two operating paths when one complete switching slice fails.
|
| 01 | How are the forty outputs of ICS Triplex T8451C divided for field-power distribution? | They are organized as five power groups, with eight output channels in each group. |
| 02 | Which load-current limits must be checked before wiring ICS Triplex T8451C? | Allow no more than 2 A continuous per channel and observe the temperature-dependent total and per-group current limits. |
| 03 | Why can an unused ICS Triplex T8451C channel report a no-load condition? | Automatic line monitoring expects current above the no-load threshold, so a suitable dummy load may be required on an unused supervised output. |
| 04 | How does ICS Triplex T8451C maintain output control after one switch path fails? | Each channel has three monitored fail-safe switch paths, allowing the two surviving paths to continue carrying the load after a single-path fault. |
| 05 | What protection response does ICS Triplex T8451C apply to an output short circuit? | The channel uses electronic latching short-circuit protection and reports the resulting fault for maintenance action. |
| 06 | Which two supply ranges must be available for ICS Triplex T8451C commissioning? | Provide 20 to 32 V DC on the backplane and 18 to 32 V DC for the field-output supply. |